- Cast-in-place concrete footings and foundation walls
- Cast-in-place concrete floor slabs-on-grade
- Tilt-up concrete exterior bearing walls
- Structural steel-framed floors with concrete on composite steel deck
- Structural steel and Open web joist-framed primary
- Typical column bays: 30' x 45'
- Floor-to-floor heights: 14'-0"
- Design live loads: Roof (snow loading) - 30 psf
Roof (equipment zone) - as required
Typical office floor - 100 psf
- Variable-volume (VAV) air-conditioning system
- Two 190-ton self-contained AC units with natural gas reheat coil
- Fan-powered VAV terminals spaced at a maximum 1000 sf per unit
- VAV electric coil heating at perimeter zones
- Air-supply medium and low-pressure ducts with slot and perforated diffusers
- Air return via ceiling plenum
- Exhaust system connected to energy recovery ventilator
- Public toilet cores per floor
- Three wet-stack risers roughed-in for future tenant use on each floor
- Automatic sensor-operated flush valves and faucets
- Automatic sprinklers: light hazard per NFPA 13
- Main service: 4000 amp, 480 volt, 3 phase, 4 wire system
- Tenant allowances: 8.0 watts/sf at 208/120V for heating
1.3 watts/sf at 277 for Lighting from the common panel
4.0 watts/sf at 208/120V for Power Outlets,
1.0 watts/sf at 208/120V Miscellaneous
- Distribution: Two electric closets per floor
- Emergency power: Base building life safety systems
- Fire alarm: "Point addressable" voice-alarm notification system
- IT Pathways: Empty conduit network for future tenant feeds
- Telephone: Primary phone service routed to two closets on each floor
- Cable: Primary cable service routed to two closets on each floor
- Satellite: Future conduits to roof for future satellite
|


|
| |