STRUCTURAL SYSTEM

  • Cast-in-place concrete footings and foundation walls
  • Cast-in-place concrete floor slabs-on-grade
  • Tilt-up concrete exterior bearing walls
  • Structural steel-framed floors with concrete on composite steel deck
  • Structural steel and Open web joist-framed primary
  • Typical column bays: 30' x 45'
  • Floor-to-floor heights: 14'-0"
  • Design live loads:     Roof (snow loading) - 30 psf        
                                   Roof (equipment zone) - as required
                                   Typical office floor - 100 psf

MECHANICAL SYSTEM - OFFICE BUILDING

  • Variable-volume (VAV) air-conditioning system
  • Two 190-ton self-contained AC units with natural gas reheat coil
  • Fan-powered VAV terminals spaced at a maximum 1000 sf per unit
  • VAV electric coil heating at perimeter zones
  • Air-supply medium and low-pressure ducts with slot and perforated diffusers
  • Air return via ceiling plenum
  • Exhaust system connected to energy recovery ventilator

PLUMBING SYSTEM

  • Public toilet cores per floor
  • Three wet-stack risers roughed-in for future tenant use on each floor
  • Automatic sensor-operated flush valves and faucets
  • Automatic sprinklers: light hazard per NFPA 13

ELECTRICAL SYSTEM

  • Main service:                 4000 amp, 480 volt, 3 phase, 4 wire system
  • Tenant allowances:         8.0 watts/sf at 208/120V for heating
                                         1.3 watts/sf at 277 for Lighting from the common panel
                                         4.0 watts/sf at 208/120V for Power Outlets, 
                                         1.0 watts/sf at 208/120V Miscellaneous
  • Distribution:                  Two electric closets per floor
  • Emergency power:          Base building life safety systems
  • Fire alarm:                    "Point addressable" voice-alarm notification system
  • IT Pathways:                  Empty conduit network for future tenant feeds
  • Telephone:                     Primary phone service routed to two closets on each floor
  • Cable:                            Primary cable service routed to two closets on each floor
  • Satellite:                        Future conduits to roof for future satellite

 